CR 027 | UP TO 650W
Applies to: Semiconductor fan heater prevents formation of condensation and frost and provides an evenly distributed interior air temperature in enclosures with electric/electronic components. The integrated thermostat is used to set the desired temperature.
download> Compact heater > Optical indicator
> Integrated thermostat > Temperature safety cut-out
> Clip fixing
Semiconductor fan heater prevents formation of condensation and frost and provides an evenly distributed interior air temperature in enclosures with electric/electronic components. The integrated thermostat is used to set the desired temperature.
Semiconductor Fan Heater CR 027 Series
Art. No. | Operating voltage | Heating capacity1 (50Hz) | Heatig capacity1 (60Hz) | Inrush current max. | Recommended pre-fuse T (time-delay) | Airflow, free flow | Setting range thermostat2 | Weight (approx.) |
---|---|---|---|---|---|---|---|---|
02700.0-00 | 220-240VAC, 50/60Hz | 475W | 550W | 11.0A | 10.0A | 35m3/h | 0 to +60°C | 0.9kg |
02701.0-00 | 220-240VAC, 50/60Hz | 550W | 650W | 13.0A | 10.0A | 45m3/h | 0 to +60°C | 1.1kg |
02700.9-00 | 100-120VAC, 50/60Hz | 400W | 550W | 14.0A | 10.0A | 35m3/h | +32 to +140°F | 0.9kg |
02701.9-00 | 100-120VAC, 50/60Hz | 510W | 650W | 15.0A | 10.0A | 45m3/h | +32 to +140°F | 1.1kg |
1 at +20°C (+68°F) ambient temperature; 2 Switch temperature difference 7K (±4K tolerance)
Heating element | PTC resistor - temperature limiting |
---|---|
Temperature safety cut-out | to protect against overheating in case of fan failure, automatic reset |
Axial fan, ball bearing | airflow see table service life 50,000h at +25°C (+77°F) |
Connection | 2-pole clamp 2.5mm2, clamping torque 0.8Nm max |
Casing | plastic according to UL94 V-0, light grey |
Optical indicator | thermostat control lamp |
Mounting | clip for 35mm DIN rail, EN 60715 |
Fitting position | vertical airflow (air outlet up) |
Dimensions | 100 x 128 x 165mm |
Operating/Storage temperature | -45 to +70°C (-49 to +158°F) |
Operating/Storage humidity | max. 90% RH (non-condensing) |
Protection type/Protection class | IP20 / II (double insulated) |
Approvals | VDE, UL File No. E204590, EAC |