RCE 016 | 5 W,9 W
Applies to: Small heaters designed to prevent condensation and to ensure a minimum operating temperature in small enclosures. The heaters are designed for permanent operation.
download> Wide voltage range > Energy saving
> Dynamic heating up > Compact
Small heaters designed to prevent condensation and to ensure a minimum operating temperature in small enclosures. The heaters are designed for permanent operation.
Small Semiconductor Heater RCE 016 Series
Art. No. | Heating capacity2 | Inrush current max. | Recommended pre-fuse T (time-delay) | Surface temperature (approx.) | Connection | Weight (approx.) |
---|---|---|---|---|---|---|
01622.0-00 | 5W | 2.0A | 2.0A | +165°C | 2 x AWG 22 cable (silicone) | 20g |
01623.0-00 | 9W | 2.5A | 4.0A | +175°C | 2 x AWG 22 cable (silicone) | 20g |
Operating voltage | 120-240V AC/DC1 (min. 110V, max. 265V) |
---|---|
Heating element | PTC resistor, temperature limiting |
Heater body | aluminium |
Mounting | see Accessories |
Fitting position | variable |
Dimensions | length 45mm, ? 10mm |
Operating/Storage temperature | -45 to +70°C (-49 to +158°F) |
Operating/Storage humidity | max. 90% RH (non-condensing) |
Protection type/Protection class | IP54 / II (double insulated) |
Approvals | VDE, UL File No. E150057 (according to UL 508A, NITW File on request), EAC |
Accessories | mounting clips (see illustration), Art. No. 09008.0-01 |
Note | other voltages on request |
1 Operating with voltages below 140V AC/DC reduces heating performance by approx. 10%.
2 at +20°C (+68°F) ambient temperature.