色婷婷国产综合激情看片_欧美日韩亚洲丝袜乱_www在线播放日本_天堂AV无码AV毛片毛_国产AV麻豆密桃无码久久_亚洲成人精品小说在线观看_亚洲网站免费_香蕉视频.app下软件_日韩视频在线一区_无码国产精品一区二区色欲

PRODUCT

PRODUCT

ELECTRONIC HYGROTHERM WITH EXTERNAL SENSOR
  • ELECTRONIC HYGROTHERM WITH EXTERNAL SENSOR
  • ELECTRONIC HYGROTHERM WITH EXTERNAL SENSOR
ELECTRONIC HYGROTHERM WITH EXTERNAL SENSOR

ETF 012

Applies to: The electronic hygrotherm senses the ambient temperature and relative humidity in an enclosure with electric/electronic components and turns on a heater (or alternatively a fan) at either set point, helping prevent the formation of condensation in the enclosure. Due to its wide voltage range the hygrotherm can be utilised anywhere in the world. The external sensor can be positioned freely anywhere in the enclosure for precise measurements.

download
  • > Temperature and humidity adjustable

  • Wide voltage range

  • Operating temperature down to -40°C

  • High switching capacity

  • With external sensor

The electronic hygrotherm senses the ambient temperature and relative humidity in an enclosure with electric/electronic components and turns on a heater (or alternatively a fan) at either set point, helping prevent the formation of condensation in the enclosure. Due to its wide voltage range the hygrotherm can be utilised anywhere in the world. The external sensor can be positioned freely anywhere in the enclosure for precise measurements.

TECHNICAL DRAWING



Electronic Hygrotherm with external sensor ETF 012


Art. No. Cable 1mArt. no. Cable 2mOperating voltageSetting range temperatureSetting range humidity
01231.0-0001231.0-01100-240VAC, 50/60Hz (min. 90VAC, max. 265VAC)0 to +60°C50 to 90% RH
01231.9-0001231.9-01100-240VAC, 50/60Hz (min. 90VAC, max. 265VAC)+32 to +140°F50 to 90% RH
01231.1-0001231.1-0124-48VDC (min. 20VDC, max. 60VDC)0 to +60°C50 to 90% RH


TECHNICAL DATA


Switch difference (temperature)2K (±1K tolerance) at +25°C (+77°F), 50% RH
Switch difference (humidity)4% RH (±1% tolerance) at +25°C (+77°F), 50% RH
Reaction time (humidity)approx. 5 sec.
Contact typechange-over contact (relay)
Service lifeVDE: NO/NC > 15,000 cycles
UL: NO/NC > 30,000 cycles
Max. switching capacity (relay output)240VAC, 10 (1.6) A
60VDC, 0.6A1
Max. inrush currentAC 30A for 10 sec.
Optical indicatorLED
Connection5-pole terminal, clamping torque 0.5Nm max.:
rigid/stranded2 wire 2.5mm2 (AWG 14)
Mountingclip for 35mm DIN rail, EN 60715
Casingplastic according to UL94 V-0, light grey
Dimensions77 x 60 x 43mm
Weightapprox. 0.2kg
Fitting positionvertical
Operating/Storage temperature-40 to +60°C (-40 to +140°F)
Operating/Storage humiditymax. 90% RH (non-condensing)
Protection typeIP20
ApprovalsVDE, UL File No. E164102, EAC

1 not UL confirmed

2 When connecting with stranded wires, wire end ferrules must be used.