SWITCH MODULE

DCM 010 | DC 20 TO 56 V

Applies to: The switch module is used to control DC powered devices with high capacities in control and switch cabinets. It is controlled via an external potential-free contact (thermostat or hygrostat), which is connected between terminal 3 and 4. It must be ensured that the external contact is suitable to switch the required signal current without any problems.

download
  • > High DC switching capacity

  • Variety of applications

  • Wide DC voltage range

  • Simple connection

The switch module is used to control DC powered devices with high capacities in control and switch cabinets. It is controlled via an external potential-free contact (thermostat or hygrostat), which is connected between terminal 3 and 4. It must be ensured that the external contact is suitable to switch the required signal current without any problems.

TECHNICAL DRAWING



Switch Module DCM 010 (DC 20 to 56 V)


Art. No.Max. switching capacityOperating temperature
01010.0-00DC 15 A-40 °C to +40 °C (-40 °F to +104 °F)
01010.0-10DC 13 A-40 °C to +50 °C (-40 °F to +122 °F)
01010.0-20DC 11 A-40 °C to +60 °C (-40 °F to +140 °F)


TECHNICAL DATA


Contact typecontact maker normally open (MOSFET)
Service life> 100,000 cycles
Operating voltageDC 20 to 56 V
Control contact – signal current3 mA at DC 20 V / 4.5 mA at DC 24 V
14 mA at DC 48 V / 17 mA at DC 56 V
Connection6-pole terminal: stranded wire1 1.5 mm2 (AWG 16);
max. 2.5 mm2 (AWG 12)
Mountingclip for 35mm DIN rail, EN 60715
Casingplastic according to UL94 V-0, grey (bicolor)
Dimensions93 x 53 x 44 mm
Weightapprox. 65 g
Fitting positionvertical
Operating temperaturesee article table below
Storage temperature-40 to +80 °C (-40 to +176 °F)
Operating/Storage humiditymax. 90 % RH (non-condensing)
Protection typeIP20
ApprovalsUL File No. E342261, VDE, EAC
Noteother versions on request

1 When connecting with stranded wires, wire end ferrules must be used.